Readings that actually tell you something
A chiller log is only useful if it records the same things each time: leaving and returning water temperatures, ambient temperature, suction and discharge pressures, compressor current, and the condition of the condenser. Those figures, taken together, show whether the machine is working harder than it was last quarter.
Approach temperature, the difference between the refrigerant and the water it is cooling, is the most telling single number. A widening approach usually means a fouled condenser or a charge problem, and it shows up long before an alarm.
The condenser is where efficiency lives
Most older chillers lose efficiency through the condenser, not through the compressor. Dust, pollen, coastal salt and, on water-cooled machines, scale all reduce heat transfer. Cleaning is unglamorous and it is the highest-value maintenance item on the plant.
Water-cooled machines depend on a water-treatment regime. If that has lapsed, cleaning alone will not restore performance, and the tubes may need more than a brush.
Controls, safety devices and records
Safety controls exist to stop a machine destroying itself, and a machine that trips repeatedly is telling you something. Recording each trip, with the conditions at the time, is how an intermittent fault is eventually found.
Control settings should be reviewed when a building's use changes. A sequence set for full occupancy will waste energy in a half-empty building, and a schedule that no longer matches tenancy is one of the easiest savings to find.
In short
- Record the same readings every visit so trends are visible.
- Approach temperature is the clearest early indicator of declining performance.
- Condenser cleaning is the highest-value routine task on most plant.
- Review control sequences whenever occupancy or tenancy changes.
Questions on this topic
How often should readings be taken?
At every service visit as a minimum. For critical plant, a monthly log taken by site staff adds real value because it catches a drift between visits.
Can I clean the condenser myself?
Air-cooled coils can often be cleaned by site staff with care, but water-cooled tubes and anything involving refrigerant or electrical work need a technician.
What does a widening approach temperature mean?
Usually that heat transfer has degraded, most often from a fouled condenser, though low charge or flow problems can also show it. It warrants investigation, not adjustment.